The UV flame detector boiler version watches the burner flame through a threaded port on the boiler front and reports what it finds to the burner control panel. It runs on DC24V and leaves the enclosure with two independent signals: a relay contact rated 2 A at 220 V, and a 4–20 mA analog output. A microcontroller inside handles the signal processing, real-time numbers appear on the digital display, and the buttons on the unit let a fitter trim the response on site without a laptop.
The connection is what makes this the boiler version. A threaded body screws onto the common couplings, valves and cooling-air pipes already fitted around most boiler sighting ports, so replacing a scanner usually means unscrewing the old unit and screwing this one in — no new bracket, no cut-out, no re-machined port. Where the old detector hung off a flat bracket instead, the flare version of the same detector is the one that fits.
Fitters know the unit by its red cylindrical housing and the specification nameplate on the side; the metal threaded base and the side hex plug are what they work with during fitting. Combustion engineers specify it for new boiler builds and burner retrofits, maintenance teams keep one on the shelf as a spare, and integrators wire it into the panels they assemble for a boiler house.
It suits boilers that need a definite answer at light-off: flame proved before the fuel valve opens, and flame loss signalled before the furnace fills with unburnt fuel.
The detector picks up a lighter's ultraviolet flame at 4 metres, which is the figure to plan a sighting run around. A lighter is a small, weak source at that distance; a burner flame is a far larger one, but the optical path still decides what reaches the sensor — the length of the sighting tube, how clean the window is, and whether steam, dust or the shape of the flame cuts across the line of sight. In an industrial boiler flame safety monitoring system the useful question is not the number on a datasheet but whether the port gives an uninterrupted view of the flame root, and that is settled at the boiler front.
Because the detector works on the ultraviolet output of the flame rather than on visible brightness, a glowing firebrick or a hot furnace wall does not read the way a flame reads. It answers to what the flame itself emits in the ultraviolet band.
Inside, a microcontroller does the processing and the buttons shift the response to suit the installation — a long, dirty sighting path needs a different setting from a short, clean one. The digital display shows real-time numbers throughout, which is what makes commissioning practical: you can watch the reading rise as the burner lights, settle as the flame steadies, and see exactly what the detector is being given before you hand the interlock over to it.
Adjustment is a matter of watching a steady flame and setting the point where the detector holds reliably, not the point where it only just triggers. A setting that works on a good day will trip the boiler on a humid one.
| Product | UV flame detector boiler version |
| Supply voltage | DC24V |
| Output 1 | Relay contacts, 2 A / 220 V |
| Output 2 | Analog 4–20 mA |
| Detection range | Lighter flame up to 4 m |
| Signal processing | Internal microcontroller |
| Adjustment | Push buttons on the unit |
| Indication | Digital display, real-time readings |
| Mounting | Threaded connection for couplings, valves and cooling-air pipes |
| Explosion protection | EXdⅡCT6 Gb |
| Body | Cylindrical housing with metal threaded base and side hex plug |
The EXdⅡCT6 Gb marking on the nameplate tells a hazardous-area assessor what the enclosure was built to: flameproof construction for group IIC gases, temperature class T6, equipment protection level Gb. In plain terms, the enclosure is designed to contain an internal ignition instead of letting it escape into the surrounding atmosphere, which is why the joints, the cover fixings and the cable entry are part of the protection rather than just packaging.
That makes it the right detector for boiler fronts inside a classified area, for fired heaters in refining and petrochemical units, and for coking or coal-chemical plant where the burner port sits in a gas-hazardous zone. Where the boiler front is unclassified the same detector still does the job; the marking simply is not the deciding factor there.
Handling rules matter as much as the marking. Do not file, machine, paint or scrape the flamepath faces while cleaning or fitting, keep the joint faces clean and undamaged, use the cover fixings the enclosure came with, and bring the cable in through a certified gland suited to the enclosure. Never open the cover while the area is live.
For the plant file, keep the two things separate: the zone classification belongs to your site, and the hardware is limited to what its marking covers. A unit that has been dropped, dented or opened for repair should be replaced rather than returned to service, because the protection depends on the enclosure being exactly as it left the factory.
Routine work on the detector is almost entirely about the window. How often it needs cleaning depends on the fuel, the dust loading and whether cooling air is connected; start with a monthly look at the reading and let the trend set the interval from there. A pulverised-coal or biomass boiler will want attention more often than a gas-fired packaged unit, and a boiler that runs continuously will teach you more in a month of analog trend than any schedule written on paper.
Clean the window with a soft cloth and a solvent that will not attack the glass or the paint, never with a scraper or an abrasive. While the unit is out, check that the sighting tube is clear and that nothing has been left in the port after work on the burner. Re-seat it in the same position and confirm the reading returns to where it was before you started.
Watch the 4–20 mA signal for drift rather than waiting for a trip. A slow decline over weeks is normally fouling; a sudden step is normally a wiring or supply problem; a reading that jumps while the burner is steady usually means the aim has moved or combustion has changed.
Do not open the enclosure while the area is live, and do not file or scrape the flamepath faces when cleaning the threads. If the detector has been damaged, replace it — a repaired flameproof enclosure no longer carries the protection it was built with.
Keep one spare detector set to the same configuration, with the settings written on the maintenance sheet, so a failed unit becomes a changeover rather than an investigation.
Not every buyer arrives knowing which item in the range fits. Tell us what the part has to do, the space it goes into and the supply you have, and our engineers check it against the specifications we publish and tell you which model matches — and when a standard item will not do. The same team designs, builds and tests the products in our own plant in Shaanxi: 28 people, 16 patents, national high-tech enterprise status, in business since 2018. They answer questions before you order, stay reachable afterwards for fitting questions and fault-finding, and take custom or non-standard requests directly.
In most cases, yes. The threaded connection is made for the couplings, valves and cooling-air pipes that surround boiler sighting ports, so a replacement usually screws onto what is already there. The thread is the deciding detail — send a photograph of the port with the boiler make, and we will check the unit against it before it is built. It is worth doing: an industrial boiler flame safety monitoring system is judged on how reliably it proves flame at light-off, and a detector that does not seat squarely on the port cannot see the flame root properly.
Mounting, mainly. Both run on DC24V, both give a relay contact plus a 4–20 mA output, and both use a microcontroller with a digital display and button adjustment. The UV flame detector boiler version fixes by thread to couplings, valves and cooling-air pipes on a boiler front. The flare version uses a flat mounting bracket for a flare stack or pilot where there is no threaded port to screw into. The port decides which one you need.
It depends on the port and the furnace. Cooling air keeps the front of the unit cooler and helps hold the window clear, which matters most on solid-fuel, biomass and waste-heat boilers where radiant heat and dust arrive together. If the port already has a cooling-air connection, keep it in service. If it never had one, tell us the furnace temperature and how the port is positioned and we will say whether your installation needs it.
The detector is built for DC24V. Check that the panel's 24 V rail can carry it alongside everything already connected, and that polarity and earthing match your drawing. Where the panel uses 110 V or 220 V control, keep the detector on 24 V and let the relay contact do the switching between the two voltages.
Yes. The response is set with the buttons on the unit, and the digital display shows real-time readings while you do it, so a fitter can watch the numbers move as the burner lights and settles. Set it against a steady flame rather than during the first seconds of light-off, and write the final setting on the maintenance sheet — that note is what turns the next replacement into a quick changeover.
It describes a flameproof enclosure for group IIC gases at temperature class T6, equipment protection level Gb — the level generally required for Zone 1. What it does not do is classify your area; that assessment belongs to your plant. Ask for the certificate copy with the order so it can go into the area file, and check it against the zone drawing before installation. Once fitted, the protection depends on the enclosure staying as it was built: no filing or painting of the joint faces, the original cover fixings, and the cable brought in through the entry it was designed for.