• TYH-1 Ultraviolet Flame Detector,MY SHOP,TYH-1 Ultraviolet Flame Detector
  • TYH-1 Ultraviolet Flame Detector,MY SHOP,TYH-1 Ultraviolet Flame Detector

TYH-1 Ultraviolet Flame Detector 4 metres as long as the ultraviolet strength is there

TYH-1 Ultraviolet Flame Detector
Works with DC24V, plus or minus a bit
Receives inputs from TYT-1 probe
Offers a relay contact (0.3A) that's closed when a flame is picked up and open if there's none
Can spot a lighter’s flame from as far as 4 metres as long as the ultraviolet strength is there
Designed to fit a C45 rail, 35mm wide
Download
View all downloads
  • TYH-1 Ultraviolet Flame Detector,MY SHOP,TYH-1 Ultraviolet Flame Detector

Description

Product Overview

Burner and boiler panels need one answer quickly and unambiguously: is there a flame, or is there not? This ultraviolet flame detector gives that answer as a relay contact rather than a measurement — closed while the flame is seen, open the moment it is not. A TYT-1 probe fixed at the burner does the looking; the electronics that read it sit on a rail inside the panel.

Splitting the two is the practical part. The probe is the only piece exposed to heat, dirt and draught at the burner front, while everything that might need adjusting or replacing stays back in the cabinet. The housing is a plain green rail module with terminal blocks along both sides and a red indicator light, so it takes its place in the same row as breakers and contactors and is wired like any other panel device.

It suits plants that want a simple flame-present signal rather than an analog reading, and panel builders who repeat the same function across a batch of burners. Where the sensing head has to sit out at the boiler front in a hazardous area, an explosion proof UV flame scanner for industrial boilers is the part that goes outside, and this unit handles the signal behind it.

Specifications

ParameterDetail
Supply voltageDC24V
Sensor inputTYT-1 ultraviolet probe
OutputOne relay contact, rated 0.3 A
Contact stateClosed while flame is present; open when no flame is seen
Working detection distanceUp to about 4 m, depending on the ultraviolet strength of the flame
Mounting35 mm C45 rail
Typical locationInside the burner or boiler control panel

Signal Path & Relay Output

  • Where the signal starts — a TYT-1 probe sighted on the flame collects the ultraviolet and passes it back to the rail unit on its probe cable; the unit turns that into a yes or a no.
  • What comes out — one relay contact and nothing else: closed while flame is detected, open when the flame is gone. No analog output to scale, no display to read.
  • Why a contact rather than an analog signal — it drops straight into a burner controller input, a PLC digital card, an alarm circuit or an interlock chain, with no signal conditioning to add.
  • The direction it fails in — because the contact holds closed only while flame is seen, a lost flame, a broken probe lead and a dead supply all look the same at the control input. Check that your logic reads an open contact the way you intend.
  • Commissioning check — light the burner and watch the contact change state at the control input; that single check proves the probe sees the flame and the wiring reaches the right terminal.
  • Kept at the edges — supply and output land on the terminal blocks along the sides of the housing, so wiring stays at the edge of the module instead of crossing the middle of the panel.
  • Matched parts from one maker — as a combustion flame detector supplier we build the probe, the probe cable and this unit, so a replacement works with what is already on the burner rather than being close enough.

Rail Mounting & Wiring

  1. Isolate the panel and confirm what is feeding the unit: it runs on 24 V DC with a small tolerance either side, and it is not a mains device.
  2. Clip the module onto a 35 mm C45 rail, in the same row as the breakers and contactors, and pick a position with room at both ends for the terminal screws and for wires to dress away cleanly.
  3. Wire the supply to the input terminals and take the relay contact out to the burner controller or PLC input, keeping this wiring physically apart from ignition and high-voltage pulse cables.
  4. Run the probe cable from the TYT-1 probe to the unit along the panel frame rather than through the ignition cable bundle, and leave enough slack at the probe end for the probe to be withdrawn for cleaning.
  5. Power up with no flame in front of the probe and confirm the contact reads open at the control input, not only at the module.
  6. Establish a flame and confirm the contact closes and the controller sees it. If the state reads inverted, correct it in the wiring or the logic now, before the boiler is handed over.
  7. Mark the rail position and terminal numbers on the panel drawing, and note where the probe is sighted from, so the next technician finds both without tracing cables.

Detection Distance & Probe Placement

Distance in an ultraviolet detector is a statement about the flame as much as about the unit. The working distance quoted for this model assumes the flame is putting out enough ultraviolet to be seen and that the sight line between probe and flame is reasonably clear. A small pilot viewed through a long, dirty sight tube can be missed at a fraction of that distance, while a bright flame on a short, open sight path is easy work.

Four things shorten the reading: a sight tube that narrows the cone of view; soot, oil mist or dust on the probe window; smoke or draught crossing between probe and flame; and a flame that is small and blue rather than bright and ultraviolet-rich. Aim at the base of the flame where it is anchored at the burner rather than at the tip, and keep the sight path as short and as open as the burner design allows.

Stray ultraviolet causes trouble from the other direction — a welding set working on the same unit, sunlight falling through an open door, or hot refractory glimpsed through the same opening. These are placement problems rather than faults in the unit, which is why the probe is aimed and shaded instead of being screwed to the nearest convenient boss.

Where the mounting boss runs hot, a purge or cooling-air arrangement is normal practice on this type of installation: it keeps the probe window clear and the probe body cooler than the radiant heat around it. Heat on its own does not call for an explosion proof UV flame scanner for industrial boilers; a classified area at the boss does.

Typical Installations

  • Small and medium boiler panels — one contact into the burner controller, proving the pilot before the main fuel valve is allowed to open.
  • Retrofits of an ageing flame box — where a probe is already fitted at the burner and the old amplifier keeps dropping out, the rail unit takes over the decision without touching the field side.
  • Process heaters and furnace pilots — a repeatable flame or no-flame signal for the interlock chain, with nothing to scale after wiring.
  • OEM burner builders — one unit per burner, the same footprint and the same terminals, so every panel in a batch is built and tested the same way.
  • Test and research benches — rigs where a low-voltage DC supply and a dry contact are easier to log than a field detector with a display and an analog output.
  • Applications that only need a yes or a no — plants that want to know the flame is there without trending its intensity; this ultraviolet flame detector gives the answer and nothing extra to interpret.

Matching & Ordering Notes

  1. Confirm the supply in the panel and that the low-voltage rail has capacity for one more device before the order is placed.
  2. Confirm the probe: say whether a TYT-1 is already fitted at the burner or has to come with the unit, and measure the run from probe to panel so the probe cable is made to that distance.
  3. Confirm what the contact will switch — a controller input, a PLC card, a relay coil — and check the rating against it. A wrong assumption here shows up at commissioning, not at the desk.
  4. Confirm which side of the panel the sensing head sits on, and whether that position falls in a classified hazardous area — the answer changes what the order has to include.
  5. Confirm the spares you want to hold. The probe lives in the heat and dirt and is the part that ages, so a spare probe is the sensible item on the shelf while the rail unit stays protected in the cabinet.
  6. Confirm the documentation for your panel file. As a combustion flame detector supplier we can send a terminal and wiring drawing with the unit — say what your records require before the order goes in.
  7. Confirm packing, delivery time and payment terms with your sales contact when the order is placed; they are agreed per order and per destination rather than being fixed here.

Probe Retrofit & Fault Finding

  • What a retrofit usually keeps — where the burner already carries a TYT-1 probe and its lead, that field hardware stays in place and only the rail unit is new. This ultraviolet flame detector reads the TYT-1 and no other probe type, so read the marking on the probe already fitted before the order is written.
  • When the probe joins the order — a sensing head of another make, one that has sat in the boss for years, or a lead shortened during an earlier repair cannot be assumed to suit. Ordering probe, lead and rail unit together puts the whole signal path on one specification.
  • The boss before the electrics — the probe has to screw into the existing sight boss, sit square on the flame and still pull out for cleaning. A seized thread, a cross-threaded coupling or a boss that has been welded over will stop commissioning long before the wiring does.
  • Condition of the old probe — a clouded window, heat scale on the shell or a stiff, cracked lead is what usually sits behind a flame signal that comes and goes. Clean the window and re-aim the probe before blaming the electronics.
  • First check, with a lighter — with the burner shut down, hold a lighter flame close in front of the probe and watch the relay contact at the control input. A contact that changes state proves probe, lead and rail unit are alive together and sends you looking elsewhere.
  • If nothing changes, work back — check the lead for continuity and for a short between core and screen at the rail unit's terminals, then repeat the lighter test with a known-good probe. If the contact returns with the substitute probe, the rail unit is cleared and the old probe is the part to replace.
  • Where failures actually sit — the probe carries the window, the heat and the dirt; the rail unit has none of them and lives in the cabinet. Keep one spare probe on the shelf and treat the controller as the last suspect, not the first.

Contact Rating & Load Matching

Load to be switchedWhat it drawsHow to arrange it
Burner controller flame inputMilliamp-level current at the controller's own input voltageWire the contact straight in; the input draws far less than the 0.3 A the contact is rated for.
PLC digital input cardA few milliamps, usually at 24 V DCDirect connection works — treat the contact as a voltage-free input and follow the card's manual for how that input is fed.
24 V DC interposing relay coilCoil current that varies with the relay chosenCheck the coil's pick-up and holding current against 0.3 A, fit a flyback diode across the coil, and let the relay's own contact carry the heavier load.
Contactor or solenoid coilPick-up current several times the holding current, then a switch-off spikeNever switch it directly: the inrush can pit or weld the contact. The interposing relay takes this duty.
Lamp, buzzer or annunciatorA cold filament draws more at switch-on than once it is litUse an LED indicator or a relay, and compare the running current with the rating before wiring it in.
Two duties on one contactThe sum of every current the contact carriesAdd them up against 0.3 A; if the total sits close to the rating, split the duties over a relay with two contacts rather than paralleling contacts.
Commissioning measurementThe real current, measured with the load energisedTake it in series or with a clamp, record the figure on the panel sheet and leave it where the next technician will find it.

Technical Support & Model Matching

Not every buyer arrives knowing which item in the range fits. Tell us what the part has to do, the space it goes into and the supply you have, and our engineers check it against the specifications we publish and tell you which model matches — and when a standard item will not do. The same team designs, builds and tests the products in our own plant in Shaanxi: 28 people, 16 patents, national high-tech enterprise status, in business since 2018. They answer questions before you order, stay reachable afterwards for fitting questions and fault-finding, and take custom or non-standard requests directly.

FAQ

Which probe should be paired with this ultraviolet flame detector?

The TYT-1 probe. The rail unit reads that probe's ultraviolet signal and nothing else, so the probe type has to match. A probe of another type, or one whose window and lead have been in service for years, is worth checking before it is reused. If a TYT-1 is already fitted at the burner and giving a clean view of the flame, it can stay where it is and only the rail unit is replaced.

Can the relay contact switch a contactor coil directly?

No — it is a signalling contact and its rating is modest. It is meant to drive a controller input, a PLC digital card, an alarm or an interlock, where the current is small. A contactor coil or a solenoid draws far more, especially at the instant it closes, so put an interposing relay in between: the contact drives the relay coil and the relay carries the heavy load. Compare the rating in the specifications with the coil you intend to switch before the panel is wired.

Do I need an explosion proof UV flame scanner for industrial boilers instead of this unit?

They answer different parts of the same question. This is a rail-mount control module that lives inside the panel; a field-rated detector is the part that sits at the boiler front where a hazardous area classification applies. If the sensing head must be mounted in the hazardous zone, order the field-rated device for that position. Where the probe can be sighted from a safe location, the rail unit and its probe cover the same duty with less hardware to install.

Will the contact chatter if the flame flickers?

A flame sitting right at the edge of detection can make the signal pulse, and the contact follows it. The fix is almost always at the probe rather than in the unit: aim for a solid view of the flame root, keep the window clean, and shorten the sight path if the burner design allows. A steady, well-sighted flame gives a steady contact.

How do I tell whether the probe or the control unit has failed?

Start at the probe. A sooted window, a crushed or damp lead, or a probe knocked out of line accounts for most cases where the contact stays open with a flame burning. Clean or re-aim the probe and watch the contact at the control input; if a known-good probe brings the contact back, the unit was never at fault. The rail unit itself has no moving parts and sits in the cabinet, away from the heat and dirt that wear the probe.