Burner and boiler panels need one answer quickly and unambiguously: is there a flame, or is there not? This ultraviolet flame detector gives that answer as a relay contact rather than a measurement — closed while the flame is seen, open the moment it is not. A TYT-1 probe fixed at the burner does the looking; the electronics that read it sit on a rail inside the panel.
Splitting the two is the practical part. The probe is the only piece exposed to heat, dirt and draught at the burner front, while everything that might need adjusting or replacing stays back in the cabinet. The housing is a plain green rail module with terminal blocks along both sides and a red indicator light, so it takes its place in the same row as breakers and contactors and is wired like any other panel device.
It suits plants that want a simple flame-present signal rather than an analog reading, and panel builders who repeat the same function across a batch of burners. Where the sensing head has to sit out at the boiler front in a hazardous area, an explosion proof UV flame scanner for industrial boilers is the part that goes outside, and this unit handles the signal behind it.
| Parameter | Detail |
|---|---|
| Supply voltage | DC24V |
| Sensor input | TYT-1 ultraviolet probe |
| Output | One relay contact, rated 0.3 A |
| Contact state | Closed while flame is present; open when no flame is seen |
| Working detection distance | Up to about 4 m, depending on the ultraviolet strength of the flame |
| Mounting | 35 mm C45 rail |
| Typical location | Inside the burner or boiler control panel |
Distance in an ultraviolet detector is a statement about the flame as much as about the unit. The working distance quoted for this model assumes the flame is putting out enough ultraviolet to be seen and that the sight line between probe and flame is reasonably clear. A small pilot viewed through a long, dirty sight tube can be missed at a fraction of that distance, while a bright flame on a short, open sight path is easy work.
Four things shorten the reading: a sight tube that narrows the cone of view; soot, oil mist or dust on the probe window; smoke or draught crossing between probe and flame; and a flame that is small and blue rather than bright and ultraviolet-rich. Aim at the base of the flame where it is anchored at the burner rather than at the tip, and keep the sight path as short and as open as the burner design allows.
Stray ultraviolet causes trouble from the other direction — a welding set working on the same unit, sunlight falling through an open door, or hot refractory glimpsed through the same opening. These are placement problems rather than faults in the unit, which is why the probe is aimed and shaded instead of being screwed to the nearest convenient boss.
Where the mounting boss runs hot, a purge or cooling-air arrangement is normal practice on this type of installation: it keeps the probe window clear and the probe body cooler than the radiant heat around it. Heat on its own does not call for an explosion proof UV flame scanner for industrial boilers; a classified area at the boss does.
| Load to be switched | What it draws | How to arrange it |
| Burner controller flame input | Milliamp-level current at the controller's own input voltage | Wire the contact straight in; the input draws far less than the 0.3 A the contact is rated for. |
| PLC digital input card | A few milliamps, usually at 24 V DC | Direct connection works — treat the contact as a voltage-free input and follow the card's manual for how that input is fed. |
| 24 V DC interposing relay coil | Coil current that varies with the relay chosen | Check the coil's pick-up and holding current against 0.3 A, fit a flyback diode across the coil, and let the relay's own contact carry the heavier load. |
| Contactor or solenoid coil | Pick-up current several times the holding current, then a switch-off spike | Never switch it directly: the inrush can pit or weld the contact. The interposing relay takes this duty. |
| Lamp, buzzer or annunciator | A cold filament draws more at switch-on than once it is lit | Use an LED indicator or a relay, and compare the running current with the rating before wiring it in. |
| Two duties on one contact | The sum of every current the contact carries | Add them up against 0.3 A; if the total sits close to the rating, split the duties over a relay with two contacts rather than paralleling contacts. |
| Commissioning measurement | The real current, measured with the load energised | Take it in series or with a clamp, record the figure on the panel sheet and leave it where the next technician will find it. |
Not every buyer arrives knowing which item in the range fits. Tell us what the part has to do, the space it goes into and the supply you have, and our engineers check it against the specifications we publish and tell you which model matches — and when a standard item will not do. The same team designs, builds and tests the products in our own plant in Shaanxi: 28 people, 16 patents, national high-tech enterprise status, in business since 2018. They answer questions before you order, stay reachable afterwards for fitting questions and fault-finding, and take custom or non-standard requests directly.
The TYT-1 probe. The rail unit reads that probe's ultraviolet signal and nothing else, so the probe type has to match. A probe of another type, or one whose window and lead have been in service for years, is worth checking before it is reused. If a TYT-1 is already fitted at the burner and giving a clean view of the flame, it can stay where it is and only the rail unit is replaced.
No — it is a signalling contact and its rating is modest. It is meant to drive a controller input, a PLC digital card, an alarm or an interlock, where the current is small. A contactor coil or a solenoid draws far more, especially at the instant it closes, so put an interposing relay in between: the contact drives the relay coil and the relay carries the heavy load. Compare the rating in the specifications with the coil you intend to switch before the panel is wired.
They answer different parts of the same question. This is a rail-mount control module that lives inside the panel; a field-rated detector is the part that sits at the boiler front where a hazardous area classification applies. If the sensing head must be mounted in the hazardous zone, order the field-rated device for that position. Where the probe can be sighted from a safe location, the rail unit and its probe cover the same duty with less hardware to install.
A flame sitting right at the edge of detection can make the signal pulse, and the contact follows it. The fix is almost always at the probe rather than in the unit: aim for a solid view of the flame root, keep the window clean, and shorten the sight path if the burner design allows. A steady, well-sighted flame gives a steady contact.
Start at the probe. A sooted window, a crushed or damp lead, or a probe knocked out of line accounts for most cases where the contact stays open with a flame burning. Clean or re-aim the probe and watch the contact at the control input; if a known-good probe brings the contact back, the unit was never at fault. The rail unit itself has no moving parts and sits in the cabinet, away from the heat and dirt that wear the probe.